Practical Overview of PFAS National Drinking Water Regulation
Explore the key aspects of the PFAS National Primary Drinking Water Regulation, including MCLs, rounding requirements, Hazard Index, PQLs, rule deadlines, and reporting guidelines. Learn about practical information on compound levels, hazard assessment, monitoring procedures, and compliance deadlines.
Download Presentation

Please find below an Image/Link to download the presentation.
The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author. If you encounter any issues during the download, it is possible that the publisher has removed the file from their server.
You are allowed to download the files provided on this website for personal or commercial use, subject to the condition that they are used lawfully. All files are the property of their respective owners.
The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author.
E N D
Presentation Transcript
PFAS - National Primary Drinking Water Regulation (NPDWR) Presented By: Sierra Bettis Guam Environmental Protection Agency
Topics Final Maximum Contaminant Levels (MCLs) Rounding Requirements Hazard Index (HI) Practical Quantitative Levels (PQLs) Rule Deadlines Reporting
Rule Overview PRACTICAL QUANTITATION LEVELS FINAL MCLG FINAL MCL TRIGGER LEVEL COMPOUND PFOA 0 4.0 ppt 2.0 ppt 4.0 ppt PFOS 0 4.0 ppt 2.0 ppt 4.0 ppt PFHxS 10 ppt 10 ppt 5 ppt 3.0 ppt PFNA 10 ppt 10 ppt 5 ppt 4.0 ppt HFPO-DA (GenX) 10 ppt 10 ppt 5 ppt 5.0 ppt Mixture of 2 or more: PFHxS, PFNA, HFPO- DA, and PFBS (Hazard Index) 1 1 0.5 N/A (unitless) (unitless) (unitless)
Rounding Calculation of the running annual average (RAA) PFOS and PFOA have 2 significant figures PFHxS, PFNA, GenX, and the Hazard Index (HI) have 1 significant figure Rounding occurs after the RAA
Hazard Index Hazard Index (HI) - mixture of 2 or more chemicals Hazard Quotient (HQ) / Health Based Water Concentration (HBWC) HQ = ratio of measured concentration in drinking water to the HBWC HBWC = the level below where there are no known adverse health effects over time of exposure and allows for margins of safety If the HI > than 1 (unitless) = exceedance of the MCL HI Equation: ((HFPO-DA/10 ppt) + (PFBS/2000 ppt) + (PFNA/10 ppt) + (PFHxS/10 ppt))
Practical Quantitation Levels (PQLs) COMPOUND FINAL MCL PQLs Sample results below the PQL will be 0 for MCL compliance Sample results below the PQL be used to determine Trigger Levels PFOA 4.0 ppt 4.0 ppt PFOS 4.0 ppt 4.0 ppt PFHxS 10 ppt 3.0 ppt PFNA 10 ppt 4.0 ppt HFPO-DA (GenX) 10 ppt 5.0 ppt Hazard Index 1 (unitless) N/A
Rule Deadlines Initial Monitoring - Completed by April 26, 2027 Surface water systems Quarterly monitoring within a 12-month period Groundwater systems greater than 10,000 customers Quarterly monitoring within a 12-month period Groundwater systems serving less than 10,000 customers Monitor twice within a 12-month period PWSs must include results of their PFAS initial monitoring into their CCRs PWSs must start issuing public notification for any monitoring and testing procedure violations
Rule Deadlines Compliance Monitoring - Beginning on April 26th, 2029 PWSs must comply with all regulated PFAS MCLs PWSs must provide notification to the public of results Based on results from initial monitoring: Quarterly monitoring - greater than the trigger level for all regulated PFAS Annual monitoring - below the trigger level for all regulated PFAS Triennial monitoring - below the trigger level for all regulated PFAS for 3 consecutive years of annual monitoring Triennial monitoring - below the trigger level for an entry point for all regulated PFAS
Reporting Tier 2 Public Notice (PN) - MCL/MRDL/TT Violation Delivered within 30 days after learning of the violation Systems will be required to provide Tier 2 notifications starting in 2029 Tier 3 Public Notice (PN) - Monitoring and Testing Procedure Violation Delivered within 1 year after learning of the violation Systems will be required to provide Tier 3 notifications starting in 2027
Calculation Examples - PFOS MCL EX 1: 1ST QUARTER PFOS = 6.2 ppt; 2ND QUARTER PFOS = 2.1 ppt ; 3RD QUARTER PFOS = 3.5 ppt ; 4TH QUARTER PFOS = 5.1 ppt
Calculation Examples - PFOS MCL EX 1: 1ST QUARTER PFOS = 6.2 ppt; 2ND QUARTER PFOS = 2.1 ppt ; 3RD QUARTER PFOS = 3.5 ppt ; 4TH QUARTER PFOS = 5.1 ppt RAA: 6.2 + 0 + 0 + 5.1 = 11.3/4 = 2.825 ppt
Calculation Examples - PFOS MCL EX 1: 1ST QUARTER PFOS = 6.2 ppt; 2ND QUARTER PFOS = 2.1 ppt ; 3RD QUARTER PFOS = 3.5 ppt ; 4TH QUARTER PFOS = 5.1 ppt RAA: 6.2 + 0 + 0 + 5.1 = 11.3/4 = 2.825 ppt Rounded to: 2.8 ppt NO MCL EXCEEDANCE
Calculation Examples - PFOS MCL EX 1: 1ST QUARTER PFOS = 6.2 ppt; 2ND QUARTER PFOS = 2.1 ppt ; 3RD QUARTER PFOS = 3.5 ppt ; 4TH QUARTER PFOS = 5.1 ppt RAA: 6.2 + 0 + 0 + 5.1 = 11.3/4 = 2.825 ppt Rounded to: 2.8 ppt NO MCL EXCEEDANCE but EXCEEDS THE TRIGGER LEVEL OF 2.0 ppt because of the quarter 1 and quarter 3 sample results
Calculation Examples - Hazard Index (HI) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt
Calculation Examples - Hazard Index (HI) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt ((HFPO-DA/10 ppt) + (PFBS/2000 ppt) + (PFNA/10 ppt) + (PFHxS/10 ppt))
Calculation Examples - Hazard Index (HI) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt ((HFPO-DA/10 ppt) + (PFBS/2000 ppt) + (PFNA/10 ppt) + (PFHxS/10 ppt)) Quarter 1: 0 + 0 + (10.2 ppt /10 ppt) + (11.0 ppt /10 ppt) = 1.02 + 1.10 = 1.12
Calculation Examples - Hazard Index (HI) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt ((HFPO-DA/10 ppt) + (PFBS/2000 ppt) + (PFNA/10 ppt) + (PFHxS/10 ppt)) Quarter 1: 0 + 0 + (10.2 ppt /10 ppt) + (11.0 ppt /10 ppt) = 1.02 + 1.10 = 1.12 RAA for HI: 1.12 + 2.09 + 1.77 + 1.74 = 6.72/4 = 1.68
Calculation Examples - Hazard Index (HI) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt ((HFPO-DA/10 ppt) + (PFBS/2000 ppt) + (PFNA/10 ppt) + (PFHxS/10 ppt)) Quarter 1: 0 + 0 + (10.2 ppt /10 ppt) + (11.0 ppt /10 ppt) = 1.02 + 1.10 = 1.12 RAA for HI: 1.12 + 2.09 + 1.77 + 1.74 = 6.72/4 = 1.68 Rounded to: 2 MCL EXCEEDANCE OF THE HI
Calculation Examples ARE WE DONE?
Calculation Examples - PFHxS MCL (EX2 Continued) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt
Calculation Examples - PFHxS MCL (EX2 Continued) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt RAA for PFHxS: 11.0 + 9.2 + 9.5 + 8.3 = 38/4 = 9.5 ppt
Calculation Examples - PFHxS MCL (EX2 Continued) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt RAA for PFHxS: 11.0 + 9.2 + 9.5 + 8.3 = 38/4 = 9.5 ppt Rounded to one significant figure = 10 ppt NO MCL EXCEEDANCE OF PFHxS
Calculation Examples - PFHxS MCL (EX2 Continued) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt RAA for PFHxS: 11.0 + 9.2 + 9.5 + 8.3 = 38/4 = 9.5 ppt Rounded to one significant figure = 10 ppt NO MCL EXCEEDANCE OF PFHxS but EXCEEDS THE TRIGGER LEVEL OF 5.0 ppt
Calculation Examples ARE WE DONE?
Calculation Examples - PFNA MCL (EX2 Continued) EX 2: 1ST QUARTER PFHxS = 11.0 ppt, PFNA = 10.2 ppt; 2ND QUARTER PFHxS = 9.2 ppt, PFNA = 11.7 ppt; 3RD QUARTER PFHxS = 9.5 ppt, PFNA = 8.2 ppt; 4TH QUARTER PFHxS = 8.3 ppt, PFNA = 9.1 ppt RAA for PFNA: 10.2 +11.7 + 8.2 + 9.1 = 39.2/4 = 9.8 ppt Rounded to one significant figure = 10 ppt NO MCL EXCEEDANCE OF PFHxS but EXCEEDS THE TRIGGER LEVEL OF 5.0 ppt