Power System Analysis: Unsymmetrical Fault Analysis Overview
Explore the analysis of unsymmetrical faults in power systems, including single line-to-ground, line-to-line, and double line-to-ground faults. Learn about fault scenarios and boundary conditions, symmetrical components, voltage calculations, sequence networks, Thevenin impedance, and more. Gain insights into understanding different types of faults and analyzing fault currents effectively.
Download Presentation
Please find below an Image/Link to download the presentation.
The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author. If you encounter any issues during the download, it is possible that the publisher has removed the file from their server.
You are allowed to download the files provided on this website for personal or commercial use, subject to the condition that they are used lawfully. All files are the property of their respective owners.
The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author.
E N D
Presentation Transcript
EEE 333 Power System Analysis Unsymmetrical Fault Analysis Unsymmetrical Fault Analysis Prepared by Dr. Md. Rezwanul Ahsan Assistant Professor, Dept. of EEE
Lecture Contents Unsymmetrical Faults Different Types of Faults (S-L-G, L-L and L-G) Analysis @Rezwan
Learning Outcomes The students will be able to Understand different types of unsymmetrical faults Analyze single line-to-ground fault, line-to-line fault and double line-to-ground fault @Rezwan
Single Line-to-Ground Fault Figure shows a 3-phase generator with neutral grounded through a impedance Zn. Suppose a line-to-ground fault occurs on phase a through impedance Zf. Assuming the generator is initially on no-load, the boundary conditions at the fault point are: Substituting for Ib=Ic=0, the symmetrical components of currents are: @Rezwan
Single Line-to-Ground Fault Then, we find that Phase a voltage in terms of symmetrical components is: ??0= 0 ?0?? ??1= ?? ?1?? ??2= 0 ?2?? 0 Then, we have 1 2 0, we get Substituting ??= ???? and ??= 3?? The fault current is, @Rezwan
Single Line-to-Ground Fault Substituting for the symmetrical components of currents in the given equations, the symmetrical components of voltage and phase voltages at the point of fault are obtained. ??0= 0 ?0?? ??1= ?? ?1?? ??2= 0 ?2?? 0 1 2 Sequence network connection (in series) for line-to-ground fault as below. For line-to-ground faults, the Thevenin impedance to the point of fault is obtained for each sequence networks are placed in series. In general, the positive- and negative-sequence impedances are equal. If the generator neutral is solidly grounded, ??= 0 and for bolted fault ??= 0. @Rezwan
Line-to-Line Fault Figure shows a 3-phase generator with a fault through an impedance Zf between phases b and c. Assuming the generator is initially on no-load, the boundary conditions at the fault point are: Substituting for ??= 0 and ??= ??, symmetrical components of currents are: @Rezwan
Line-to-Line Fault From here, we get Then, we find that, Again we get, Substituting for ??1 and ??2, considering ?? 1= ?? 2, we get ??0= 0 ?0?? ??1= ?? ?1?? ??2= 0 ?2?? 0 1 Substituting for ??, we get 2 Since ? ?2 ?2 ? = 3, solving for ?? 1 results in @Rezwan
Line-to-Line Fault The phase currents are: The fault current is ??= ??= ?2 ? ?? or ??= ? 3?? 1 1 ??0= 0 ?0?? ??1= ?? ?1?? ??2= 0 ?2?? 0 Substituting the symmetrical components of currents, the symmetrical components of voltage and phase voltages at the point of fault are obtained 1 2 @Rezwan
Line-to-Line Fault By connecting the positive- and negative-sequence networks in opposite as shown in the equivalent circuit. In practical, the positive- and negative- sequence impedances are found to be equal. For a bolted fault, ??= 0 @Rezwan
Double Line-to-Ground Fault Figure shows a 3-phase generator with a fault on phases b and c through an impedance Zf to ground. Assuming the generator is initially on no-load, the boundary conditions at the fault point are: The phase voltages ??and?? are: ?= ?? ? Since, ??= ?? then we get ?? @Rezwan
Double Line-to-Ground Fault Substituting the symmetrical components of currents, then we have 1 + ? + ?2= 0 ? then we have Substituting ?? and ?? ?= ?? ? ?? ? Substituting symmetrical components of voltage and solving for ?? then we get ??0= 0 ?0?? ??1= ?? ?1?? ??2= 0 ?2?? 0 (i) 1 2 ?= ?? ? we get Similarly, for ?? (ii) @Rezwan
Double Line-to-Ground Fault And finally, from ??= ?? 0+ ?? 1+ ?? 2= 0 we have (iii) Observing equations (i), (ii) & (iii) it can be concluded that the positive- sequence impedance in series with the parallel combination of the negative- and zero-sequence networks as shown in the equivalent circuit in the Figure below. The phase currents can be calculated and finally the fault current is obtained from @Rezwan
Example 10.5 The one-line diagram of a simple power system is shown below. The neutral of each generator is grounded through a current limiting reactor of 0.25/3 per unig on a 100- MVA base. The generators are running on no-load at their rated voltage and rated frequency with their emfs in phase. Determine fault current for the following faults: (a) A balanced 3-phase fault at bus 3 through a fault impedance ??= ?0.1 per unit (b) A single line-to-ground fault at bus 3 through a fault impedance ??= ?0.1 per unit (c) A line-to-line fault at bus 3 through a fault impedance ??= ?0.1 per unit (d) A double line-to-ground fault at bus 3 through a fault impedance ??= ?0.1 per unit @Rezwan
Example 10.5 The positive-sequence impedance network is shown in Figure below. Combining parallel branches, the positive-sequence Thevenin impedance is @Rezwan
Example 10.5 Since the negative-sequence impedance of each element is the same as the positive-sequence impedance, we have ?33 2= ?33 1= ?0.22 @Rezwan
Example 10.5 The equivalent circuit for zero-sequence network is constructed according to transformer winding connection and given in Figure below. Delta to Wye conversion Combining the parallel branches, the zero-sequence Thevenin impedance is @Rezwan
Example 10.5 (a) Balanced 3-phase fault at bus 3: Assuming no-load generated emfs are equal to 1.0 per unit, the fault current is: (b) Single line-to-ground fault at bus 3: The sequence components of the fault currents are: The fault current is @Rezwan
Example 10.5 (c) Line-to-line fault at bus 3: The zero-sequence component of current is zero, ?3 The positive-and negative-sequence components of the fault current are 0= 0 The fault current is (d) Double line-to-ground fault at bus 3: The positive-sequence components of the fault currents is: The negative-sequence component of current is: @Rezwan
Example 10.5 The zero-sequence component of current is: And the phase currents are: The fault current is @Rezwan